Plans are required prior to the issuance of any kind of permit.
AUTOMATIC FIRE SPRINKLER PLAN SUBMITTALS REQUIREMENTS:
- Plan size shall be no smaller than 24”x36
- Scale shall be no smaller than 1/8”= 1 foot
- A minimum of three (3) sets of plans is required
- A minimum of two (2) sets of hydraulic calculations is required
- Proof calculations may be required.
- Full height section of the structure is required showing slopes, beams and other architectural features that may affect discharge patterns.
- Current water availability documentation shall accompany all submittals of new systems and TI additions to mra.
- Installation must be by currently licensed c16 contractors.
- A full set of sprinkler plans must be maintained on the job site for rough and final inspections.
- Underground piping installations by other than sprinkler contractor must be approved prior to approval of fire sprinkler plans.
- Smoke detectors are required.
- A minimum one (1) inch water meter is required.
All plan checks are done at the San Gabriel Fire Prevention Bureau.
|

|



|

|

|